Our Brands

Schneider Electric USA Website

Welcome to our website.
		
How can we help you today?
What is the function of the undervoltage trip for the Powerpact P-frame, R-frame, and NS630b - NS3200 electronic trip circuit breakers?
Issue:
What is the function of the undervoltage trip for the Powerpact P-frame, R-frame, and NS630b - NS3200 electronic trip circuit breakers?

Product Line:
Molded case circuit breakers.

Environment:
Products sold in the United States.

Cause:
Product features.

Resolution:
The undervoltage trip accessory trips the circuit breaker when the voltage drops to a value between 35% and 70% of the control voltage. If the undervoltage trip is not energized, it is impossible to close the circuit breaker, either manually or electrically. An attempt to close the circuit breaker produces no movement of the main contacts. Closing is allowed when the supply voltage of the undervoltage trip reaches 85% of the rated voltage.


Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings