Our Brands

Schneider Electric USA Website

Welcome to our website.
		
How can we help you today?
Does Square D offer a stainless steel NEMA 4 wireway the same as Hoffman?
Issue:
Is Wireway available in stainless steel?

Product Line:
Wire Management

Environment:
Wireway

Resolution:
Square D does not offer Nema 4/4X stainless steel wireway.

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Help and Contact Center
  • Contact Sales
  • Find our Offices
  • Where to Buy
  • Tech Support: 877-342-5173
  • Careers
  • Company Profile
  • Investors
  • Newsroom
  • Report a Misconduct
  • Product Documentation
  • Software and Firmware
  • Product Selector
  • Product Replacement
  • DigestPLUS Online Catalogue
  • Blog
  • Events
  • Schneider Electric Community
  • Sustainability
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings