How many terminals do the equipment ground kits PKOGTA4, PKOGTA6, PKOGTA7, and PKOGTA8 have and what wire sizes do they accept?
Issue:
Product Design Features

Product Line:
Heavy Duty Safety Switches

Resolution:
1) The PKOGTA4 has 4 separate lugs in the kit and each lug will accept (1) #6 - 250 kcmil Al/Cu conductor

2) The PKOGTA6 has 6 terminals and each terminal will accept (1) #14 - #1/0 Al/Cu conductor
NOTE: the PKOGTA6 contains 1 ground bar with the 6 holes and is approximately 4.61 inches long

3) The PKOGTA7 has 8 terminals and each terminal will accept (1) #4 - 350 kcmil  Al/Cu conductor
NOTE: the PKOGTA7 contains 2 ground bars, each bar has 4 holes and is approximately 5.50 inches long

4) The PKOGTA8 has 8 terminals and each terminal will accept (1) #4 - 350kcmil Al/Cu conductor
NOTE: the PKOGTA8 contains 2 ground bars, each bar has 4 holes and is approximately 5.50 inches long

Schneider Electric USA

Explore more
Product:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Product:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings