Our Brands

Schneider Electric USA Website

Welcome to our website.
		
How can we help you today?
What is the piston actuator assembly for a 9012 GCW1,21 GCWM1,21 GFW1,21 GFWM1,21 series B or C?
Piston actuator assembly 9998PC270. This is also used on 9012 products beginning with GJ, GQ and GT.


CTA-ID : 15386

Schneider Electric USA

Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings