Our Brands

Schneider Electric USA Website

Welcome to our website.
		
How can we help you today?
Can a 2p, QO-GFI branch breaker be used in a QO24L70F, QO24L70S, QO2L40RB, or QO24L70RB load center?
Issue:
Product features

Product Line:
QO load centers

Resolution:
Yes, but those load centers only have adequate wire bending space for a maximum #10 AWG wire. This will restrict the QO-GFI breaker to a maximum of 30 amperes.

Schneider Electric USA

Explore more
Product:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Product:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings