Our Brands

Schneider Electric USA Website

Welcome to our website.
		
How can we help you today?
Is the inhibit thermal imaging feature of either the full function test kit (FFTK) or handheld test kit (HHTK) supported in all trip units?
Issue:
Can the FFTK or HHTK inhibit thermal imaging?

Product Line:
Molded Case Circuit Breaker Trip Unit Accessory

Resolution:
The handheld test kit (S33594) and the full function test kit (S33595) cannot inhibit thermal imaging on standard trip units (2.0, 3.0 and 5.0). It is designed for the A, P, and H trip units.

Note: For non-communicating Micrologic, ET, and STR trip units, a 15 minute delay must be observed to allow reset of thermal memory.

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings