Issue:
ST-20 Standard for Transformers
Product Line:
LV Transformers
Environment:
Applies to Low Voltage Transformers by SquareD/Schneider Electric
Cause:
Transformer testing
Resolution:
Every SquareD/Schneider Electric Low Voltage Dry Type Distribution Transformer receives and must pass the following tests per NEMA ST-20 before it is allowed to leave the factory:
Visual
Polarity and Phase Relation
Ratio-tests
No-load Losses and excitation Current
Dielectric - Applied potential and Induced potential
As well, there are additional tests completed per NEMA ST-20 on first design of each transformer rating:
Impedance
Load Loss
Dielectric - Impulse
Audible Sound Level
ST-20 Standard for Transformers
Product Line:
LV Transformers
Environment:
Applies to Low Voltage Transformers by SquareD/Schneider Electric
Cause:
Transformer testing
Resolution:
Every SquareD/Schneider Electric Low Voltage Dry Type Distribution Transformer receives and must pass the following tests per NEMA ST-20 before it is allowed to leave the factory:
Visual
Polarity and Phase Relation
Ratio-tests
No-load Losses and excitation Current
Dielectric - Applied potential and Induced potential
As well, there are additional tests completed per NEMA ST-20 on first design of each transformer rating:
Impedance
Load Loss
Dielectric - Impulse
Audible Sound Level
Released for: Schneider Electric USA








Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales inquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Center
Find support resources for all your needs, in one place.