Our Brands

Schneider Electric USA Website

Welcome to our website.
		
How can we help you today?
What is the amount of current imbalance required to trip the feature unit 9065 solid state overload relay?
Issue:
When will a Solid State Overload trip when there is current Imbalance

Product Line:
NEMA and Definite Purpose Contactors and Starter

Environment:
9065 Solid State Overload Relay

Resolution:
The unit is guaranteed to trip within 3 seconds at 25% phase current imbalance. It will start tripping at +/- 17% imbalance.

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings