Are any of the QO breakers rated to accept 2 conductors under 1 terminal?

Product Line:
Miniature Circuit Breakers

Resolution:
Yes, 10 to 30 A QO breakers are rated to accept 2 conductors under 1 terminal for copper wire size #14-#10.
The breakers are also rated to accept 1 conductor for wire size #14-#8 Cu or Al.

Applies to QO and QOB, 1, 2, and 3 pole, 10 to 30 A
Does not apply to QOT breakers.
Does not apply to breakers with suffix GFI, AFI, CAFI, DF, EPD, or EPE.