Where is the best place to mount a QO2175SB secondary surge arrestor in a QO load center?
Issue:
Product installation feature

Product Line:
QO load centers and Surge protective devices

Resolution:
The QO2175SB can be mounted anywhere in the QO panel, but ideally should be located as close to the mains as possible. The neutral conductor should be routed and connected to the panel's neutral assembly in the shortest distance possible.