Our Brands

Schneider Electric USA Website

Welcome to our website.
		
How can we help you today?
Can two branch neutral wires (or grounded conductors) be installed in the same neutral bar terminal in a QO or Homeline load center?
Issue:
Product Features

Product Line:
QO and HOMELINE Load Centers

Resolution:
No. The National Electrical Code (NEC) does NOT allow for this and the article in the current code would read something similar to this; "Each grounded conductor shall terminate within the panelboard in an individual terminal that is not also used for another conductor. Exception: Grounded conductors of circuits with parallel conductors shall be permitted to terminate in a single terminal if the terminal is identified for connection of more than one conductor."

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings