Our Brands

Schneider Electric USA Website

Welcome to our website.
		
How can we help you today?
How to order ohase loss protection in a 8502/8536/8538/8539 Contactor - Starter?
Issue:
How does one specify phase loss protection on a combination or non-combination NEMA starter?

Product Line:
NEMA and Definite Purpose Contactors and Starters

Environment:
Type S NEMA Contactors and Starters

Resolution:
Order class 8538/8539 or Class 8536/8502 with form R44. Specify voltage of motor and control devices. Provides phase failure phase reversal over and under voltage protection.

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings