Does a 9070 Type T or TF Industrial Control Transformer (CPT) have any continuous overload capacity? What about momentary overloads due to high inrush loads (a coil on a contactor?)

Issue:
Control Transformers may experience momentary overloads on high inrush loads

Product Line:
LV Transformers

Environment:
Applies to 9070 T and TF type Control Transformers by SquareD/Schneider Electric

Cause:
Inductive loads such as Motors, Solenoids, and Transformers may produce high inrush currents when first energized


Resolution:

Transformers are 100% rated devices.  As such, they do not have any continuous overload capacity.  CPTs are specifically designed for momentary currrent draw in excess of it`s rating for high inrush type loads.  For directions on selecting the appropriate CPT for Contactor or Starter applications, begin with the Inrush VA and Sealed VA of the Contactor or Starter coil.  Then, see the Regulation chart and associated instructions on page 5 of the Industrial Control Transformer catalog, document # 9070CT9901, attached below.


Schneider Electric USA

Attachment(s)
ControlXfmr.pdf [2.54 MB]
Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings