Our Brands

Schneider Electric USA Website

Welcome to our website.
		
How can we help you today?
What is the difference between AFI and GFI circuit breakers?
Issue:
Product Design Features
Product Line:
Miniature Circuit Breakers
Resolution:
The AFI is a UL listed circuit breaker designed to mitigate the effects of arcing faults. It is required by UL to protect against arcs between current carrying conductors above 75 A (Square D AFI protects from arcs above 50 A), and may trip on leakage to ground with a minimum threshold of 30 to 50 mA.
The GFI is a circuit breaker UL listed for interrupting the circuit when more than 6 mA of ground fault leakage is detected.

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings