Our Brands

Schneider Electric USA Website

Welcome to our website.
		
How can we help you today?
Can the HOM2150 and HOM2200 breakers be used as a branch circuit breaker in a Homeline load center or CSED?

Article available in these languages: Spanish

Issue:
Product Design Features

Product line:
Homeline branch breakers

Environment:
Branch breakers

Cause:
Application

Resolution:
CSED = Combination Service Entrance Devices
MB = Main Breakers


No, the HOM2150 and HOM2200 CANNOT be used as branch circuit breakers. These breakers are designed as Main Breakers that were used in obsolete design HOMELINE load centers. But they are still used in a few CSED catalog numbers as the main breakers.

NOTE: The high amperage Homeline branch breakers are part numbers HOM2150BB, HOM2175BB and HOM2200BB and these breakers can ONLY be used in the Homeline CSED that are designed to accept them, see current digest and/or wiring diagram of each specific catalog number for use.

Schneider Electric USA

Explore more
Category:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Category:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings