Our Brands

Schneider Electric USA Website

Welcome to our website.
		
How can we help you today?
What is the number of switching operations of Square D, 200 A, heavy duty, F-series safety switches?
Issue:
Application

Product Line:
HD Safety Switch

Resolution:
For safety switches, the standard for design and testing of the number of switching operations is governed by UL98 and NEMA KS-1.There are two separate tests: (1) endurance test, and (2) horsepower-overload test. The below table shows the minimum number of operations required (OFF to ON to OFF) by UL and NEMA. For the endurance test, however, Square D F-series safety switches exceed the UL and NEMA requirements by up to 3 times the total (see below table).

NUMBER OF OPERATIONS:
Table showing number of switching operations for the Square D 200 A safety switches per UL, NEMA, and Square D
* endurance test done at switch rated Load current
** horsepower test - make/break motor inrush/locked rotor current at rated HP

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings