Our Brands

Schneider Electric USA Website

Welcome to our website.
		
How can we help you today?
What is the part number for replacement 110 / 120 vac control coil for the LC1F400 contactor?
Issue:
LC1F400 replacement coil for 110/120Vac

Product Line:
IEC Contactors and Starters

Environment:
Tesys F Contactors

Resolution:
For standard coil (40 - 400 hertz) order LX1FJ110.

For low sealed consumption coil (40 - 400 hertz) which offers high tolerance to inrush voltage drops, immune to micro-breaks (main supply or contact chain) and are capable of operation on networks with harmonic numbers less than or equal to 7; order LX9FJ925.

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings