How can we help you today?

How to communicate with the Series 4000/7000 Group 5 controller via RS485?

Using ASCO 5170 (72EE2) QEM

ASCO 5170 QEM by default is configured for Ethernet communication. It should be configured first for Serial communication.

Here are the steps:
1. Open QEM.
2. Move jumper J203 to the left. This will activate Serial mode.
3. Move jumper J207 to the left. This will activate the RS-485 port.

image.png

After activating the Serial mode and RS-485 port. The following should be set accordingly:
1. Termination Resistor
2. RS-458 Connection
image.png

The next steps are to be configured on the Group 5 controller.
1. On Group 5 controller, go to Main Menu ➡ Settings ➡ General ➡ Serial Communication.
2. Select baud rate with MBUS prefix.
3. Enter the appropriate device address.
image.png

Refer to the Modus Register Map document (381339-221) for Group 5 Holding Register addresses.

imageimage

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Help and Contact Center
  • Contact Sales
  • Find our Offices
  • Where to Buy
  • Tech Support: 877-342-5173
  • Careers
  • Company Profile
  • Investors
  • Newsroom
  • Report a Misconduct
  • Product Documentation
  • Software and Firmware
  • Product Selector
  • Product Replacement
  • DigestPLUS Online Catalogue
  • Blog
  • Events
  • Schneider Electric Community
  • Sustainability
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings