Our Brands

Schneider Electric USA Website

Welcome to our website.
		
How can we help you today?
Which Miniature Circuit Breaker protection devices need to be installed with EVlink Home?
The charging station shall be protected by the following devices:
Circuit Breaker 20A Curve C for each socket 3.7 kW (1P+N)
Circuit Breaker 40A Curve C for each socket 7.4 kW (1P+N)
Circuit Breaker 20A Curve C for each socket 11 kW (3P+N)

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings