Our Brands

Schneider Electric USA Website

Welcome to our website.
		
How can we help you today?
Can the ATV212 be used at high elevation?

Issue:

Customer wants to use the ATV212 at elevation over the maximum elevation listed in the Manual (1000 meters).

Product Line:

Altivar 212

Environment:

Altitude over 1000 meters

Cause:

High elevation jobsite

Resolution:

The ATV212 products is limited at 1000m without derating.

You can reach 3000m with current derating 1 % per 100m.

The limit is 2000m for Corner grounded system.

We can not be higher because the rated insulation of the product is designed for altitude up to 3000m.

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings