Our Brands

Schneider Electric USA Website

Welcome to our website.
		
How can we help you today?
How can I upgrade the firmware of a BMEAHI0810 module with a PC located on the Control Network of the BMENOC0321 ?

The gateway address of the BMEAHI0810 module must correspond to the IP address of the fieldbus network managed by the BMENOC0321.

For example, in the Ethernet Network Manager screen shown below, the gateway of the AHI module is set to the IP address of the router:


BMEAHI0812, Gateway,BMENOC0321

In the BMEAHI0812 DTM instance, you need to enable the option "Firmware upgrade"  as follow :

EnableFirmwareUpgrade

And always perform a transfer to FDR server after each modification of the BMEAHI0812 DTM instance.
Next, open Unity Loader and connect to the IP address of your BMEAHI0812 module to perform the upgrade :


BMEAHI, upgrade,Unity Loader

Schneider Electric USA

Explore more
Product:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Product:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings