Issue:
Unable to load the configuration to bus coupler TPRBC*** from Somove.

Product Line:
Tesys Island Motor Management System
Environment:
IEC Contactors and Relays
Answer:
This message is shown if the DTM tries to store a configuration to the Bus Coupler but it is rejected. This could happen if there is a mismatch between versions of the DTM and the Bus Coupler firmware. Check the compatibility matrix from the Release Notes and verify that your DTM and Firmware version match.
This message will also display if the Bus Coupler reference is inconsistent, i.e. storing a configuration for a Profinet bus coupler (TPRBCPFN) on an EtherNet/IP bus coupler (TPRBCEIP).
Unable to load the configuration to bus coupler TPRBC*** from Somove.
Product Line:
Tesys Island Motor Management System
Environment:
IEC Contactors and Relays
Answer:
This message is shown if the DTM tries to store a configuration to the Bus Coupler but it is rejected. This could happen if there is a mismatch between versions of the DTM and the Bus Coupler firmware. Check the compatibility matrix from the Release Notes and verify that your DTM and Firmware version match.
This message will also display if the Bus Coupler reference is inconsistent, i.e. storing a configuration for a Profinet bus coupler (TPRBCPFN) on an EtherNet/IP bus coupler (TPRBCEIP).