Issue:
Breaker to feed SPD SDSA1175
Product Line:
Surge Protection Device
Answer:
It has to be 2 single pole breakers
Make sure to have the SPD connected to breakers with opposing phases, one is on A phase and the other on B phase.
Have this installation approved by their electrical inspector first before doing that.