Issue: HCJ wire range
Product Line: Panelboards
Resolution: This will accept (2) 600kcmil. The (2) 600kcmil requires 16" wire bending space. There should be 16.32" available.
Released for: Schneider Electric USA


Our Brands
Schneider Electric USA Website
Issue: HCJ wire range
Product Line: Panelboards
Resolution: This will accept (2) 600kcmil. The (2) 600kcmil requires 16" wire bending space. There should be 16.32" available.