Issue:
I need the curves showing knee point of current transformers like 780R202?
Product Line:
Current transformers.
Answer:
See attached catalog.
For example:
Transformer is 780R202
The flat section is the saturation point, at point 1, you can see the gentle slope saturating at 155-160V