Our Brands

Impact-Company-Logo-English Black-01-177x54

Schneider Electric USA Website

Welcome to our website.
		
How can we help you today?
What are the approximate switchgear and device weights of the Metal Clad Arc-Resistant?

Issue:

Any job that involves moving the Metal Clad Switchgear, for instance; maintenance, storage, or commissioning, requires knowing its weight so that customers have the proper crane.

Product Line:

MV Switchgear.

Environment:

Metal Clad.

Cause:

Maintenance / Commissioning.

Resolution:

Switchgear section (one-high) 1200 & 2000A*3500  lbs (1591 kg)
Switchgear section (two-high) 1200 & 2000A*4300  lbs (1951 kg)
Switchgear section (one-high) 3000A*6000 lbs (2721 kg)
Switchgear section (one-high) 4000A with fans*6400 lbs (2900 kg)
Breaker – 1200A, 40kA380  lbs (170 kg)
Breaker – 1200A, 50kA430  lbs (195 kg)
Breaker – 2000A, 40kA450  lbs (205 kg)
Breaker – 2000A, 50kA500  lbs (225 kg)
Breaker – 3000A & 4000, 50kA700  lbs (320 kg)
Breaker – 1200, 2000, 3000 & 4000A 63kA800  lbs (363 kg)
Drawout Unit – (2) 15kV VT’s210  lbs (95 kg)
Drawout Unit – 15kVA CPT270  lbs (123 kg)
3 Arrester – 15kV Intermediate120  lbs (55 kg)

*units with control wiring, busbars, heaters and CT’s.

End Panels Left or Right side668  lbs (303 kg)
LV Box (bubble)62  lbs (28 kg)
Top Plenum176 lbs (80 kg)
Plenum extension with exhaust cover (standard length) 80”786 lbs (357 kg)
Arc Shield139 lbs (63 kg)
Additional for 12” Rear Extension245 lbs (111 kg)
Lift Truck360 s (164 kg)

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings