Our Brands

Impact-Company-Logo-English Black-01-177x54

Schneider Electric USA Website

Welcome to our website.
		
How can we help you today?
GV2 Mounted side by side: Thermal setting

Issue:

Thermal trip setting for multiple GV2 units mounted side by side.

Product Line:

IEC Contactors and Starters

Environment:

Tesys GV2 Manual Starters

Resolution:

When several products GV2ME, GV2P or GV2RT are mounted side by side, the thermal trip setting Ir may need to be adjusted up to 1.1 x Ir.

Do not exceed the maximum thermal setting Ir.

Example: GV2ME14, thermal setting range: 6-10 A, do not adjust Ir above 10A.

Schneider Electric USA

Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings