Our Brands

Schneider Electric USA Website

Welcome to our website.
		
How can we help you today?
Recommended overlap distance for busbar joints in PrismaSeT I

Design rule says that the overlap distance should be as follows:

5mm copper busbars- 5 times the thickness of secondary busbars

10mm copper busbars- 3 times the thickness of secondary busbars

Please see the images below:

image 1 image 2

However, IEC 61439 does not suggest that what should be overlap dimension. Temperature Rise test is the ultimate proof of joint resistance. All the joints are validated by Temperature Rise Test as per IEC 61439-1&2 in PrismaSeT I.

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings