Our Brands

Schneider Electric USA Website

Welcome to our website.
		
How can we help you today?
How to change decimal resolution (2 digits, 3 digits, 4 digits ect) in PME Estidama gadget Period over Period graph.

Environment:

Power Monitoring Expert 2022, 2023, 2024

----------------------------------------------------------------------

Product Line:

Estidama gadget.

----------------------------------------------------------------------

Description of the issue:

If the customer wants to change the decimal resolution of the displayed value in this gadget, then how can they do that.

----------------------------------------------------------------------

Workaround:

It can be done by editing the "EstidamaPeriodOverPeriod.JS" JavaScript file from the folder mentioned in step 1.

Step 1:

Please edit EstidamaPeriodOverPeriod.JS file from the below location and change the precision value accordingly based on the requirement.

“C:\Program Files (x86)\Schneider Electric\Power Monitoring Expert\Applications\Dashboards\Content\Gadgets\EstidamaPeriodOverPeriod”

Please refer to the below snapshot to modify the precision value.

Image 1

eg:  Customer can change the precision from 3 to 2 if the customer wants to show 2 decimal values in the report.

Step 2:

Please ensure that the program file path may be different in your installation. Help yourself to find the PME installation path, and edit the java script file.

Step 3:

Once modified, just refresh the browser.

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings