Our Brands

Impact-Company-Logo-English Black-01-177x54

Schneider Electric USA Website

Welcome to our website.
		
How can we help you today?
In EcoStruxure Operator Terminal Expert, why do my String Displays not show the text and symbols from String Variables from Modicon M241/M251/M262 PLCs?

Issue:

On my HMI Display running EcoStruxure Operator Terminal Expert, the String display is showing blank values or incorrect characters when reading from STRING type variables using the Schneider-MachineExpertNetwork driver reading from a Modicon M241, M251 or M262 PLC.

Product Line:

EcoStruxure Operator Terminal Expert

EcoStruxure Machine Expert

Environment:

HMI Configuration Software in Windows

Resolution:

For the HMI to read the STRING and WSTRING type variables via MachineExpertNetwork protocol,

  1. In EcoStruxure Operator Terminal Expert software, open your HMI project
  2. Navigate to the Project Explorer
  3. Expand Target01 > Drivers
  4. Select "Schneider Electric-MachineExpertNetwork*" node
  5. In the System Architecture page, click on the row of the Equipment (default name "MachineExpertEquipment1")
  6. On the far right side of the screen under the Properties box, find "String Encode" near the bottom of the list.
  7. In the String Encode dropdown, select "CodePage1252"
  8. Download the changes to your HMI (or Simulate)

String Encode setting in MachineExpertNetwork Driver and Equipment Settings

ALSO NOTE: The best font to use for String Displays showing String Variables from M2xx PLCs is <LanguageName>_Gothic

If this FAQ did not solve your issue, you can chat with us at chat with us or e-mail us at customer.services@se.com to create a case with our Technical Support Team.

If you are not located in North America, please contact your local Customer Care Center for assistance:

Support | Schneider Electric Global (se.com)

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings