{}

Our Brands

Impact-Company-Logo-English Black-01-177x54

Welcome to the Schneider Electric Website

Welcome to our website.
Search FAQs
You are currently viewing the content available in Vietnam. If you are looking for information for another region, please select the correct country from the top-left dropdown in the page and 'Navigate to Browse FAQs' in the Support menu.
What is the difference between ModSoft PID function and Concept PID function.

The difference between ModSoft PID and Concept PID loops are as follows:

PID (ModSoft):
PB - Gain = 100 / PB
I - Integral Coefficient Expressed as Repeats/Minute. The higher the value, the greater the integral contribution
D – Derivative Coefficient. Expressed in Minutes. The higher the value, the greater the derivative contribution
PID (Concept):
GAIN - Enter GAIN value as a REAL. Can be Positive or Negative. Positive Gain = Direct acting loop. Negative Gain = Reverse acting loop
TI - Integral Time. Expressed as TIME. The smaller the unit of time, the more significant the integration
TD - Derivative Time. Expressed as TIME. The greater the unit of time, the greater the derivative contribution.

Schneider Electric Vietnam

Explore more
Range:
Articles that might be helpful Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Explore more
Range: