Issue:
Changing the default output value showed on the display.
Product line:
Altivar ATV212
Environment:
All models, all serial numbers
Cause:
Customer preference
Resolution:
Parameter F710 sets the default display. The factory setting is 0 for motor operating frequency. Other options:
1 = speed reference
2 = motor current
3 = drive rated current
4 = drive thermal state
5 = output power
6 = PID internal speed reference
7 = serial comm data
8 = output speed
9 and 10 are communication frames received data
Changing the default output value showed on the display.