How to setup the ATV61 drive for Apogee P1 card?
Issue:
Programming Apogee P1 Card on an ATV61
Product Line:
Altivar ATV61
Environment:
All
Cause:
Programming set up assistance.
Resolution:
Menu 1.9
Address set to 0 to 99
Baud Rate: 4800, 9600, 19200, 38400, 57600, 76800
Network time out: 2 to 60 seconds
Please note you must power cycle after changing the address or Baud rate.