You are currently viewing the content available in Vietnam. If you are looking for information for another region, please select the correct country from the top-left dropdown in the page and 'Navigate to Browse FAQs' in the Support menu.
Issue:
The soft start runs the motor in reverse when in generator mode.
Product Line:
ATS48, ATS22
Environment:
All Models and serial numbers
Cause:
Motor running in reverse
Resolution:
To change the direction of the motor swap two wires feeding the soft start at the generator.
Released for: Schneider Electric Vietnam


Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales enquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Centre
Find support resources for all your needs, in one place.