You are currently viewing the content available in Vietnam. If you are looking for information for another region, please select the correct country from the top-left dropdown in the page and 'Navigate to Browse FAQs' in the Support menu.
Goals and Symptoms
Procedure for adding an IP address onto a ProworX32 project for a Momentum 171CCC9x0 x0 M1E processor.
Causes and Fixes
· Start up ProworX32
· Open your project
· Select Configuration
· Enter a value into the Config Extension Size (ex. 200)
· This value can be modified later depending on the Config Extension Used value
· Select Configuration Extensions
· Check and highlight TCP/IP
· Enter New IP and Subnet Mask info
· Save project
· Select Communications
· Select which form of connection you currently have to download your project.(Modbus, Modbus Plus or TCP/IP)
· Or enter the PRODUCTS current IP address that is stored on the processor if your just changing to a new IP address.
· Save project
· Open Controller tab
· Select Write All
· Select Write
· Make sure you get the Write to M1 960-20 Complete in the Message Central window
· Select Communications
· Enter New IP address info
· Open Controller tab
· Select Transfer to Flash/EEPROM…
· Select Transfer
· Recycle power to your Momentum processor to make sure all changes were saved
· Select Start/Stop…
· Check your logic and make sure all is fine
Released for: Schneider Electric Vietnam






Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales enquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Centre
Find support resources for all your needs, in one place.