How do I setup Vijeo Citect V7.0 for redundant LAN?

Issue:

How do I setup Vijeo Citect V7.0 for redundant LAN?

Product Line:

Vijeo Citect V7.0

Resolution:

The purpose of this resolution is to provide a solution for LAN redundancy with Vijeo Citect V7.0

This requires two NIC cards in the Vijeo Citect server PC. It is recommended to run the ethernet cable to a different path (conduit) to another ethernet switch. So that in the event of a link or ethernet switch failure, the other path may still provide data to the Vijeo Citect I/O Server

Citect Project Editor - Redundant LAN

If this FAQ did not solve your issue, you can chat with us at chat with us or e-mail us at customer.services@se.com to create a case with our Technical Support Team.