{}

Our Brands

Impact-Company-Logo-English Black-01-177x54

Welcome to the Schneider Electric Website

Welcome to our website.
Search FAQs
You are currently viewing the content available in Vietnam. If you are looking for information for another region, please select the correct country from the top-left dropdown in the page and 'Navigate to Browse FAQs' in the Support menu.
What does the 'Modbus Exception Code 03 Illegal Data Value' error mean when writing to a External Modbus Control Register on a 7650?

Product Line
ION7650/7550

Environment
Register Writing

Resolution
The meter is locked into a Read-Only mode when the password security is anything other than the default of 0 (zero).  To write to an External Modbus control registers requires password security to either be disabled, or set to 0.

Schneider Electric Vietnam

Explore more
Range:
Articles that might be helpful Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Explore more
Range: