How to connect Unity Pro to a Modbus Plus network through the MBX Gateway Driver
Issue
How can Unity Pro connect from a remote PC to a PLC on a Modbus Plus network through the MBX Gateway Driver?
Product Line
- Unity Pro
- MBX Driver Suite
Environment
- MBX Driver Suite v6.0
- MBX Gateway Client
- Modbus Plus network
Resolution
Before proceeding, the MBX Gateway Client and Server must already be configured for remote access to the Modbus Plus network.
In Unity Pro:
-
Open PLC > Set Address.
-
Enter the Modbus Plus address of the target PLC.
-
In Media, select the MB+ device corresponding to the MBX Gateway Client.
-
The device numbering used by Unity Pro is offset by 1 compared with the MBX Gateway configuration.
Example: If the MBX Gateway Client is configured as device 1, select MBPLUS02 as the Media in Unity Pro.
-
Select OK.
-
From the PLC menu, select Connect to establish the connection to the PLC.