You are currently viewing the content available in Vietnam. If you are looking for information for another region, please select the correct country from the top-left dropdown in the page and 'Navigate to Browse FAQs' in the Support menu.
Issue
User would like to know the minimum current required for CM2000 to measure current
Product
CM2000
Resolution
There must be 25 milliamps on the CT secondary or 0.5% of the CT primary ratio to wake up current readings.
For more information, see detailed datasheet here
Released for: Schneider Electric Vietnam


Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales enquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Centre
Find support resources for all your needs, in one place.