{}

Our Brands

Impact-Company-Logo-English Black-01-177x54

Welcome to the Schneider Electric Website

Welcome to our website.
Search FAQs
You are currently viewing the content available in Vietnam. If you are looking for information for another region, please select the correct country from the top-left dropdown in the page and 'Navigate to Browse FAQs' in the Support menu.
How to configure the Momentum to start in RUN mode after a power cycle using Modsoft

Issue
How to configure  a Momentum start  in 'RUN' mode after a power cycle using Modsoft.

Product Line
All Momentum PLC's.

Environment
Windows 7

Resolution
In order for the Momentum to start in RUN mode after power cycle, the program must be saved to the built-in flash.
The following steps can be used to accomplish this in 'Modsoft version 2.62.

  • Click Online\ Direct To PLC.
  • Press F2 'PlcOps'.
  • Press F2 to 'Stop the PLC'.
  • Press F8 'Save To'.
  • Type in Y for answering the question (Continue Power Down Run State?).
  • Type in Y for 'Continue'.
  • Press F1 to 'Start the PLC'.
  • Disconnect from the PLC.
  • Power cycle the PLC and it will start back up in RUN mode.

Schneider Electric Vietnam

Explore more
Range:
Articles that might be helpful Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Explore more
Range: