To communicate between PL7-Pro loaded in the programming computer and TSX37 master via Uni-Telway bus, the 'SYS' (system) address must be entered in PL7 Pro.
Note: A sufficient number of addresses must be configured in the master and addresses 1, 2 and 3 must be reserved for PL7 Pro.
To communicate between PL7-07 and TSX Nano slave via Uni-Telway bus, address 0.254.5.254.10'x' must be entered in PL7-07, where 'x' is the TSX Nano slave address.
Note: A sufficient number of addresses must be configured in the master and addresses 1, 2 and 3 must be reserved for PL7 Pro.
To communicate between PL7-07 and TSX Nano slave via Uni-Telway bus, address 0.254.5.254.10'x' must be entered in PL7-07, where 'x' is the TSX Nano slave address.