Issue:
Programming an ATV61/71 drive to show speed as percentage instead of frequency.
Product Line:
ATV61, ATV71
Environment:
All models and serial numbers
Cause:
None
Resolution:
Show Output Frequency As a Percentage- go to menu 2 , Access level = advanced or expert
- go to menu 7 , Display config menu
- go to menu 7.1, User parameters menu
- go to "Parameter selection"; choose Menu 1.2 [Monitoring].
- Select “Output Frequency”
- Esc until come back to the 7.1 User parameters menu
- Go to the "Customized selection "
- Select “Output Frequency”
- If you want to change the name from “Output Frequency to Output Percentage
- Choose “User Name”
- Turn the thumb wheel to scroll to the letter “O” then press the F3 button to move the cursor to the rightmost position, repeat selecting the next letter. (note: to move back press F2 and to end and save this custom name press enter)
- Select “Unit” and select “%”
- Select “Multiplier” and enter “10”
- Select “Divisor” and select “6”
- Press Esc back to the MAIN MENU
- Press enter on the DRIVE MENU.
- Scroll to the MONITORING menu and press enter
- Scroll to the customized “User Name” you entered above.
- You should see the output frequency shown as a percentage.
Released for: Schneider Electric Vietnam




Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales enquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Centre
Find support resources for all your needs, in one place.