Issue:
Synchronous motor set up on an ATV71
Product Line:
ATV71
Environment:
All models and serial numbers
Cause:
None
Resolution:
The CTT [Motor control type] of the ATV71 drive must be changed from the default value of UUC [SVC V] to SYn [Sync. mot]. This selection makes the asynchronous motor parameters inaccessible, and the synchronous motor parameters accessible.
The following parameters can be acquired from the motor nameplate and must be entered into the motor control menu:
Synchronous motor set up on an ATV71
Product Line:
ATV71
Environment:
All models and serial numbers
Cause:
None
Resolution:
The CTT [Motor control type] of the ATV71 drive must be changed from the default value of UUC [SVC V] to SYn [Sync. mot]. This selection makes the asynchronous motor parameters inaccessible, and the synchronous motor parameters accessible.
The following parameters can be acquired from the motor nameplate and must be entered into the motor control menu:
nCrS | Nominal sync current |
nSPS | Nominal sync mot speed |
PPnS | Pole pairs number (sync) |
PHS | Sync. EMF constant |
PrT | Power Ident. |
Released for: Schneider Electric Vietnam




Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales enquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Centre
Find support resources for all your needs, in one place.