Our Brands

Impact-Company-Logo-English Black-01-177x54

Welcome to the Schneider Electric Website

Welcome to our website.
		
How can we help you today?
You are currently viewing the content available in Vietnam. If you are looking for information for another region, please select the correct country from the top-left dropdown in the page and 'Navigate to Browse FAQs' in the Support menu.
Do the ATV61 and ATV71 Drives have a built in ON delay timer for the logic inputs?

Article available in these languages: Spanish

Issue:
Can a delay be added to the logic inputs on the ATV61 and ATV71 Drives?

Product line:
Altivar 61 & 71

Environment:
All models, all serial numbers.

Cause:
Customer needs to delay the run command after LI1 closes.

Resolution:
Using the HMI or keypad, under Menu 1.5 Inputs/Outputs CFG, go to LI1 Configuration and select LI1 On Delay.
The default setting for this parameter is 0ms, but can be set to 0 to 200ms.
The time delay function is available on all the logic inputs.

Schneider Electric Vietnam

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:

Need help?

  • Product Selector

    Quickly and easily find the right products and accessories for your applications.

  • Get a Quote

    Start your sales enquiry online and an expert will connect with you.

  • Where to buy?

    Easily find the nearest Schneider Electric distributor in your location.

  • Help Centre

    Find support resources for all your needs, in one place.

  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Find our Offices
  • Get a Quote
  • Where to buy
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings