What is the interval for the WebReach/Diagram RMS calculation
Issue
RMS calculation frequency in the Waveform display in WebReach/Diagrams is unknown and no documents explain how often the value is calculated

Product
ION Enterprise 6.0
Struxureware Power Monitoring 7.0.x
Power Monitoring Expert 7.2.x , 8.x, 9.x

Environment
Web Applications Diagrams or Web Reach

Cause
Documents do not describe how often RMS is calculated

Resolution
The interval for the RMS calculation is 1 cycle.