What are the basic wiring connections for the ATV212 drive?

Article available in these languages: Spanish

Issue:
Basic wiring for the ATV212 drive.

Product line:
ATV212, Altivar 212

Environment:
All models

Cause:
Limited wiring details provided with the drive.

Resolution:
The minimum requirements to remotely operate an ATV212 drive are a run command and a speed reference.  By default from the factory, terminal F is the run forward input.  VIA to CC is the default analog input for a 0-10Vdc speed reference.

P24 provides 24Vdc from an internal power supply, so use a dry contact closure on P24 to F.

**Note these values and assignments can be changed in the Programming.  These are the default settings only, with CMOd = 0 and FMOd = 1.

basic schematics