Issue:
ATV61 or ATV71uses 4-20mA input speed signal to control the motor speed between LSP to HSP.
Product Line:
Altivar ATV61
Environment:
All
Cause:
They have low speed LSP set to 45 hz but they want the drives analog input to allow the drive to run between 0 to 60hz not low speed to high speed.
Resolution:
The Drive wills analog inputs will allow the drive to run between Low speed to high speed. If you want to have a low speed setting above 0 and still want the drive to follow 0 to 60hz then set the Reference Template Parameter (BSP) in Menu 1.5 to Pedestal mode.
Menu 1.5 programming below.

ATV61 or ATV71uses 4-20mA input speed signal to control the motor speed between LSP to HSP.
Product Line:
Altivar ATV61
Environment:
All
Cause:
They have low speed LSP set to 45 hz but they want the drives analog input to allow the drive to run between 0 to 60hz not low speed to high speed.
Resolution:
The Drive wills analog inputs will allow the drive to run between Low speed to high speed. If you want to have a low speed setting above 0 and still want the drive to follow 0 to 60hz then set the Reference Template Parameter (BSP) in Menu 1.5 to Pedestal mode.
Menu 1.5 programming below.
Released for: Schneider Electric Vietnam




Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales enquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Centre
Find support resources for all your needs, in one place.