How do you access a bit in a word in a M221 controller using Machine Expert Basic (former SoMachine Basic) software?

Article available in these languages: Spanish

The syntax to access a bit in a word is %MWx:X where X is the offset of the bit.
Example: to turn on bit 10 of %MW20 you can use a coil with address %MW20:X10