Issue:
N/A
Product Line:
Altivar Machines, Altivar 312
Environment:
All serial numbers for ATV312
Cause:
N/A
Resolution:
No, sinking the logic inputs on an ATV312 will not work with 3 wire control. To use 3 wire control you would have to source the inputs