You are currently viewing the content available in Vietnam. If you are looking for information for another region, please select the correct country from the top-left dropdown in the page and 'Navigate to Browse FAQs' in the Support menu.
Issue:
Can the preset speeds be used when ATV212 is in local control?
Product Line:
ALTIVAR 212
Environment:
All serial number
Cause:
N/A
Resolution
No, preset speeds are not active when in local control.
Can the preset speeds be used when ATV212 is in local control?
Product Line:
ALTIVAR 212
Environment:
All serial number
Cause:
N/A
Resolution
No, preset speeds are not active when in local control.
Released for: Schneider Electric Vietnam


Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales enquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Centre
Find support resources for all your needs, in one place.